Level switch KMW is microprocessor based and can be installed in any
position in tanks or piping systems.
The measuring principle is an electromagnetic
wave (100…180MHz). A high frequency signal sweep is radiated from the sensor
tip into the tank or pipe. The medium acts as a virtual capacitor, which together
with a coil in the sensor, will form a circuit creating the switching point. This virtual
capacity will depend of the dielectric value of the medium and is well defined for
most media.
Therefore the KMW is suitable for almost all liquids and paste-like
medias.
There are 7 base settings for several medias.
To adjust the sensitivity there are two possibilities, by internal dipswitch or via PC
with software. The characteristics of the medias are visualizable and adjustable with
the PC-USB interface software.
For viscous and adhesive medias the KMW is available
with extended PEEK sensor. Applications are high and low level
detection in tanks and dry run protection of pumps in the Food & Beverage and
Pharmaceutical industry.
All common hygienic process connections are available.